CN1114 Modbus Register Table

SITE DESIGN AND CONFIGURABLE SETTINGS LIVE DATA Last update: (times shown GMT)

Modbus address LIVE MB Register Content Multiplier LIVE Parameter Value Units Parameter Name Notes
100 0 1 0 Customer ID
101 0 1 0 Site number
102 0 1 0 Building Number
103 0 1 0 Unit Number
104 0 1 0 Device ID
105 0 1 0 Number of Site Design Data Parameters i.e. size of this table, Commissioning Settings plus User Configurable settings
106 0 1 0 Number of System Parameters Controller Outputs and Calculated parameters
107 0 1 0 Number of Power Up Parameters
108 0 1 0 Number of Fans
109 0 1 0 Number of Parameters/Fan
110 0 1 0 Number of Sensors (Inputs)
111 0 1 0 Number of Parameters/Sensor
112 0 1 0 Number of Output-Modules
113 0 1 0 Number of Parameters/Output-Module
114 0 1 0 Maximum consecutive Modbus registers read/write supported by the controller
115 0 100 0 ms Slave Response Timeout Local in ms/100 controller stores this as multiples of 100ms.
116 0 10 0 m3h min_total_airflow_m3h MVR Minimum Ventilation Rate
117 0 1 0 Pa air_pressure Static building pressure
118 0 1 0 min_qty_of_running_fans Minimum quantity of running fans
119 0 1 0 s fan_cycle_period Fan cycle period if individual fan volume is lower than MinFanVent
120 0 1 0 m3/h min_fan_vent_airflow_m3h Minimum allowable volume per fan in MVR mode
121 0 0.1 0 Celsius agri_temp_hyst_times_ten NTC1 Temperature Hysteresis
122 0 0.1 0 Celsius heat_shift_fan_on_times_ten If Fans cycling, offset of Heater On threshold during Fan on period
123 0 1 0 s cooling_step_increase_delay Delay time response to cooling demand
124 0 1 0 %/10s cooling_rate_increase_cap Allowable rate of change of cooling increase per 10sec
125 0 1 0 %/10s cooling_rate_decrease_cap Allowable rate of change of cooling decrease per 10sec
126 0 1 0 m3h min_fan_cool_airflow_m3h Minimum allowable volume per fan in Cooling mode (m3/h)
127 0 0.1 0.0 Celsius agri_setpoint_temp_times_ten Required temperature of building
128 0 0.1 0.0 Celsius agri_heat_shift_temp_times_ten Offset below Setpoint to the middle of the heating band
129 0 0.1 0.0 Celsius agri_heat_temp_hyst_times_ten Heating Hysteresis
130 0 0.1 0.0 Celsius agri_cool_shift_temp_times_ten Offset above Setpoint to the middle of the cooling band
131 0 0.1 0.0 Celsius agri_cool_band_temp_times_ten Cooling band width (degC) x 10
132 0 1 0 % Cooling_Vol_Hyst_percent Hysteresis on cooling volume
133 0 1 0 RPM MB_Fan_Max_Speed Fan maximum RPM as shown in data sheet.

POWERUP LIVE DATA Last update: (times shown GMT)

Modbus address LIVE MB Register Content Multiplier LIVE Parameter Value Units Parameter Name Notes
250 0 1 0 Controller part number
251 0 1 0 Firmware part number
252 0 1 0 Firmware Issue
253 0 1 0 RCON Register Content Cause of program restart, e.g. Power Cycle, Software Watchdog, etc
254 0 1 0 Year Firmware build year 4 digits
255 0 1 0 Month Firmware build month 1-12
256 0 1 0 Day Firmware build day 1-31
257 0 1 0 Hour Firmware build hour 0-23
258 0 1 0 Minute Firmware build minute 0-59
259 0 1 0 Second Firmware build second 0-59

SYSTEM DATA LIVE DATA Last update: (times shown GMT)

Modbus address LIVE MB Register Content Multiplier LIVE Parameter Value Units Parameter Name Notes
300 0 1 0 Design data/configuration changed flag Assigned as CONFIG_CHANGED_REGISTER (Site Design/Config data changed flag)
301 0 1 see next row CONTROLLER UPTIME HIGH Controller seconds since last restart, top 16 bits of 32 bit integer, see total below
302 0 1 0 s CONTROLLER UPTIME LOW Total Controller uptime = bottom 16 bits of integer plus 0x10000 times top 16 bits
303 0 1 0 demand_airflow_0_1000 The proportion of the maximun available airflow that is being used, scaled 0-1000
304 0 1 0 reqd_Fans The number of fans needed to achieve the airflow at the applicable minimum speed
305 0 1 0 pwm_output_0_1000 The 0-10V Output level for the driven Fan Groups, scaled 0-1000
306 0 1 0 s fan_cycling_on_time Fan On time if Cycling, seconds
307 0 1 see next row tot_airflow_m3h_hi Total Airflow, top 16 bits of 32 bit integer, see total below
308 0 1 0 m3h tot_airflow_m3h_lo Total Airflow = bottom 16 bits plus 0x10000 times top 16 bits
309 0 0.01 0.00 Celsius lowest_temp_in_entire_store_times_hundred Lowest temperature stored in Heating/Cooling demand smoothing store x 100
310 0 0.01 0.00 Celsius highest_temp_in_entire_store_times_hundred Highest temperature stored in Heating/Cooling demand smoothing store x 100
311 0 1 0 cooling_mode Cooling Airflow Mode (0 if not cooling)
312 0 1 0 HeatingOn Heating On = 1, Off = 0
313 0 1 0 s previous_cooling_period Duration of last Cooling Period, seconds
314 0 1 0 s previous_heating_period Duration of last Heating Period, seconds
315 0 1 0 s previous_ventilation_period Duration of last Ventilation (no Heating or Cooling) Period, seconds

FAN LIVE DATA Last update: (times shown GMT)

Modbus address LIVE MB Register Content Multiplier LIVE Parameter Value Units Parameter Name Notes

Temperature Sensor Data

SENSOR LIVE DATA Last update: (times shown GMT)

Modbus address LIVE MB Register Content Multiplier LIVE Parameter Value Units Parameter Name Notes
64768 0 0.1 0.0 Celsius Building Temperature, degrees C For Heating or Cooling Control
64769 0 0.1 0.0 Celsius Control Room Temperature, degrees C For logging only